Electric Modulating Gate Valve

Description

TECHNICAL DATA SHEET
ELECTRIC MODULATING GATE VALVE

1. BASIC SPECIFICATIONS

Parameter Specification
Valve Type Electric Modulating Gate Valve
Operation Motorized Actuation (Modulating Control)
Power Supply 480V AC, 3-Phase, 60Hz
Control Signal Input: 4-20mA DC (Position Control)
Feedback Signal Output: 4-20mA DC (Position Feedback)
Valve Body Material Carbon Steel (ASME A216 WCB)
Seat Material Metal-to-Metal / Resilient Seated (Optional)
Gate Material Stainless Steel (SS316)
Pressure Rating ASME Class 600 / PN100
Temperature Range Standard: -20°C to +200°C
High-Temp Option: Up to +425°C

2. ACTUATOR & CONTROL

Feature Description
Actuator Type Intelligent Electric Actuator (Modulating)
Control Accuracy ±0.5% Full Stroke
Travel Time Adjustable (Typical: 60 sec for full stroke)
Duty Cycle Continuous (S2-100%)
Enclosure Rating IP67 / NEMA 4X (Weatherproof & Corrosion-Resistant)
Local Interface LCD Display + Push Buttons (Manual Override, Configuration)
Fail-Safe Option Spring-Return to Predefined Position (Open/Closed/Last)

3. ELECTRICAL & SIGNAL DETAILS

Connection Specification
Power Terminal 480V AC ±10%, 3-Phase, 3-Wire
Signal Terminal 4-20mA Input (Control) + 4-20mA Output (Position Feedback)
Communication Optional: HART, Modbus RTU, or PROFIBUS DP (Fieldbus Protocols)
Electrical Conduit 1/2″ NPT Female Ports

4. PERFORMANCE & DIMENSIONS

Parameter Value
Flow Characteristic Linear or Equal Percentage (Selectable)
Leakage Class Metal Seat: ANSI Class IV (FCI 70-2)
Soft Seat: ANSI Class VI (Bubble-Tight)
Valve Size (Typical) 2″ to 24″ (DN50 to DN600)
End Connection Flanged (ASME B16.5 RF), Wafer, or Butt-Weld
Mounting Position Any Orientation

5. CERTIFICATIONS & COMPLIANCE

  • Standards:

    • API 600 / API 603 (Gate Valves)

    • IEC 60534 (Industrial Process Control Valves)

    • SIL 2/3 Capable (IEC 61508)

  • Certifications: CE, RoHS, EAC (Customizable per region)


6. OPTIONAL FEATURES

  • Position Limit Switches (Open/Close)

  • Torque Limiting for Overload Protection

  • Heating Jacket (For Cryogenic/High-Viscosity Fluids)

  • Explosion-Proof Actuator (ATEX/IECEx Zone 1)

  • Corrosion-Resistant Coatings (Epoxy, Xylan)


7. REMARKS

  • Wiring Diagram: Included in installation manual.

  • Calibration: Field-adjustable via actuator interface.

  • Maintenance: Self-diagnostic function with fault alarm output.